DG Sets and GRAP in Delhi NCR: What Site and Facility Managers Need to Know
· By Devta Gensets team
Every winter, as air quality in Delhi NCR gets worse, the same question comes up on construction sites, in factories and at event venues: can we still run our generator? The answer depends on the size of the set, what fuel it runs on and how it controls emissions. Here is a plain summary.
Rules change and orders are updated often. Always check the latest CAQM order before relying on this summary.
Two layers of rules
CAQM Direction No. 76. Issued by the Commission for Air Quality Management on 29 September 2023 and amended since, it sets out which DG sets can be used in the NCR and what emission control each one needs. It applies all year, across industrial, commercial and residential users.
GRAP (Graded Response Action Plan). When the air quality index crosses set levels, CAQM invokes GRAP in stages, from Stage I up to Stage IV. Each stage adds restrictions. Every GRAP order also tells authorities to enforce the DG set rules from Direction No. 76 strictly, and to make sure diesel generators are not used as a regular source of power.
Which generators can run
Broadly, the sets that are treated most favourably are:
- Gas-based sets running on natural gas, LPG, biogas, propane or butane.
- New diesel sets certified to CPCB IV+, the emission standard for gensets up to 800 kW that applies to engines made from 1 July 2023.
- Older diesel sets that have been upgraded by converting to dual fuel (gas and diesel) or by fitting a certified retrofit emission control device (RECD), depending on their size.
Requirements by size for older diesel sets
For sets built to older standards, Direction No. 76 and its amendment set requirements by capacity. In simple terms:
- Below 19 kW: no retrofit route is available, so these portable sets are the most restricted during GRAP.
- 19 kW to under 41 kW (about 23 to 51 kVA): must run in dual fuel mode.
- 41 kW to under 800 kW (about 51 to 1000 kVA): dual fuel mode or a certified retrofit emission control device.
- 800 kW and above: must meet the emission control requirements set for this large category.
Sets that could not convert only because gas supply is not available have been allowed limited use for emergency services. Check the current order for the exact list.
What this means for a rented generator
If you are hiring a generator during the winter months, the simplest way to stay on the right side of the rules is to rent a set that is already compliant: a CPCB IV+ certified diesel set, or a gas or dual-fuel unit. Ask the rental company for the certification of the specific set they are sending, not just the brand.
Practical tips for winter
- Check the GRAP stage every day during the season. CAQM announces changes and they apply immediately.
- Keep the set's emission certificate and RECD or dual-fuel documents on site in case of an inspection.
- Do not plan to run a generator as your main supply if grid power is available. That is exactly what the orders target.
- If you have an old set that is not compliant, plan the upgrade or replacement before October, not during a Stage III order.